Water context
Samples: raw water and treated water from the outlet installation point
Smart Solutions for Reliable Water.Performance evidence · Retail · XSOA
MR DIY XSOA · Terusan Bojongsoang, Baleendah, Bandung Regency

“The water is cloudy and coloured. Please provide a solution so it becomes clean, clear, and suitable for daily needs.”
Samples: raw water and treated water from the outlet installation point
ARS HPFS 150 LPH was configured to address measured turbidity, colour, odour, manganese, iron, and suspended solids in the raw water.
Internal report 06/ARS-01/I/2026 concludes that the raw-water sample did not meet the report’s clean-water benchmarks for the parameters tested, while the HPFS output did.
Measured evidence
The summary below reproduces selected values from the ARS internal test report. Values must be read with the sampling date, method, and water context.
| Parameter | Before | After HPFS | Report benchmark |
|---|---|---|---|
| TurbidityFAU | 84 | 0 | <3 |
| Colourmg/L Pt-Co | 18 | 0 | 10 |
| Odour | Detected | Not detected | Not detected |
| Manganesemg/L | 0.33 | <0.1 | 0.1 |
| Iron (Fe)mg/L | 0.21 | <0.02 | 0.2 |
| TSSmg/L | 71 | 1 | — |
| pH | 6.7 | 7.7 | 6.5–8.5 |
Scope note: this internal test applies only to the submitted samples and the parameters measured on the stated date. Water quality may change. Visual clarity alone does not establish drinking-water safety; microbiological and other relevant parameters require verification according to the intended use and applicable requirements.

Sustaining performance
ARS uses the initial test as a performance baseline. Follow-up service can then be planned around source-water changes, usage load, pressure and flow, equipment condition, operating records, and repeat testing when required.
ARS case-study standard
Future projects will follow the same structure so readers can distinguish photographs, measured evidence, technical interpretation, and the plan for sustaining performance.